UL83标准THW/THHW/THW-2图1

UL83标准THW/THHW/THW-2

2022-01-17 11:030询价
价格:¥1.00/米
品牌:青凯
规格:18awg~1000Kcmil
温度:90
电压:600
起订:100米
供应:100000米
发货:15天内
 TYPE TW/THW/THW-2

Scope

This specification covers type TW/THW/THW-2 cable with soft annealed copper solid or stranded conductor and PVC insulation, conforming to Standard 83 of Underwriters Laboratories, Inc. They meet the requirements of the VW-1 flame test and oil resistant. UL file No. E210924.

Application

Type TW/THW/THW-2 are intended for general purpose applications utilized in conduit or other raceways for services, feeders and branch-circuit wiring as specified in the National Electric Code (NEC). TW is rated at a conductor temperature of 60℃ dry or wet, THW is rated at a conductor temperature of 75℃ dry or wet, THW-2 is rated at a conductor temperature of 90℃ dry or wet. They are permitted for 600V application.

Construction

Conductors: Soft annealed copper, bare or tinned.

Sizes 14AWG-2000kcmil: Solid or stranded.

Insulation: Flame retardant PVC. Thickness: per UL83.

Information  on  the  cable: AWG or kcmil size, type letters, rated voltage, the name of the manufacturer, UL file number, characteristic, manufacture date, FEET.

 

 

Table 1

Type THW-2 Cable Data

Size

AWG

Strands

No./OD.

(mm)

PVC

Insulation

Average

Thickness

(mm)

Approx.

O.D.

(mm)

Max.DC

Resistance

(20℃,

Ω/km)

(Bare Copper)

Max.DC

Resistance

(20℃,

Ω/km)

(Tinned Copper)

14

41/0.254

0.76

3.38

8.61

9.25

12

65/0.254

0.76

3.97

5.43

5.82

10

104/0.254

0.76

4.65

3.41

3.66

8

168/0.254

1.14

6.90

2.18

2.35

6

133/0.36

1.52

8.48

1.38

1.46

4

133/0.465

1.52

10.05

0.865

0.918

2

168/0.511

1.52

11.72

0.544

0.566

1

208/0.511

2.03

13.75

0.431

0.449

1/0

266/0.511

2.03

14.76

0.345

0.359

2/0

342/0.511

2.03

16.82

0.273

0.285

 