| General specifications |
| Signal type |
Analog input |
| Supply |
| Connection |
Power Rail or terminals 11+, 12- |
| Rated voltage |
20 ... 35 V DC |
| Ripple |
within the supply tolerance |
| Rated current |
< 20 mA |
| Input |
| Connection side |
field side |
| Connection |
terminals 4+, 5- |
| Input resistance |
min. 10 MΩ |
| Transmission range |
0 ... 12 V |
| Offset voltage/current |
< 2 mV / < 7 nA |
| Output |
| Connection side |
control side |
| Connection |
terminals 7-, 8+ |
| Voltage |
0 ... 12 V |
| Output resistance |
max. 20 Ω |
| Transfer characteristics |
| Cut-off frequency |
1.2 kHz (-3 dB) |
| Deviation |
|
| |
After calibration |
± 5 mV at 20 °C (68 °F) |
| |
Influence of ambient temperature |
≤ 0.005 % of range per K |
| Rise time |
≤ 0.4 ms |
| Galvanic isolation |
| Output/power supply |
functional insulation, rated insulation voltage 50 V AC |
| Indicators/settings |
| Display elements |
LED |
| Labeling |
space for labeling at the front |
| Directive conformity |
| Electromagnetic compatibility |
|
| |
Directive 2014/30/EU |
EN 61326-1:2013 (industrial locations) |
| Conformity |
| Electromagnetic compatibility |
NE 21 |
| Degree of protection |
IEC 60529 |
| Ambient conditions |
| Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
| Mechanical specifications |
| Degree of protection |
IP20 |
| Connection |
screw terminals |
| Mass |
approx. 100 g |
| Dimensions |
20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 |
| Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Data for application in connection with hazardous areas |
| EU-Type Examination Certificate |
BAS 01 ATEX 7262 |
| |
Marking |
II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C) , [circuit(s) in zone 0/1/2] |
| |
Voltage |
18 V |
| |
Current |
4.2 mA |
| |
Power |
19 mW |
| Supply |
|
| |
Maximum safe voltage |
250 V (Attention! The rated voltage is lower.) |
| Output |
|
| |
Maximum safe voltage |
250 V (Attention! The rated voltage is lower.) |
| Certificate |
baseEFA 10 ATEX 0079X |
| |
Marking |
II 3G Ex nA II T4 Gc [device in zone 2] |
| Galvanic isolation |
|
| |
Input/Output |
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| |
Input/power supply |
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity |
|
| |
Directive 2014/34/EU |
EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
| International approvals |
| FM approval |
|
| |
Control drawing |
116-0129 |
| UL approval |
|
| |
Control drawing |
116-0173 (cULus) |
| CSA approval |
|
| |
Control drawing |
116-0132 |
| IECEx approval |
|
| |
IECEx certificate |
IECEx BAS 10.0040X |
| |
IECEx marking |
Ex nA IIC T4 Gc |
| General information |
| Supplementary information |
Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Accessories |
| Optional accessories |
- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03) |